How to Size an Electric Motor: kW, HP, Torque and Speed

Key Takeaway: Size a motor from the load: Torque (Nm) = 9550 × kW ÷ rpm. Add a 10–15% margin and pick the next standard rating. Confirm speed (poles), load type, duty cycle, ambient temperature, altitude and starting method. Oversized motors run at poor power factor and efficiency.

Size for the Load, Not for the Old Nameplate

An undersized motor overheats and fails early. An oversized motor costs more to buy, runs at a poorer power factor and wastes energy at light load. Correct sizing starts from the driven machine, not from the rating of the motor that happened to be installed before.

Step 1: Establish the Power the Load Needs

Power, torque and speed are linked by one formula:

Torque (Nm) = 9550 × Power (kW) ÷ Speed (rpm)

A 7.5 kW motor running at 1440 rpm delivers 9550 × 7.5 ÷ 1440 = 49.7 Nm at full load. To convert ratings, 1 HP = 0.746 kW.

For a centrifugal pump handling water, shaft power can be estimated directly:

Power (kW) = Flow (m³/h) × Head (m) ÷ (367 × Pump efficiency)

A pump delivering 36 m³/h against a 30 m head at 65% efficiency needs 36 × 30 ÷ (367 × 0.65) = 4.5 kW at the shaft. Adding a 10–15% margin gives about 5.2 kW, so the next standard rating, 5.5 kW (7.5 HP), is the correct choice.

Step 2: Choose the Speed

Synchronous speed is set by the supply frequency and the number of poles: Speed (rpm) = 120 × Frequency ÷ Poles. On a 50 Hz supply:

  • 2-pole: 3000 rpm synchronous
  • 4-pole: 1500 rpm synchronous
  • 6-pole: 1000 rpm synchronous
  • 8-pole: 750 rpm synchronous

An induction motor runs slightly below synchronous speed at full load because of slip, which is why a 4-pole motor is typically rated near 1440 rpm. For the same power, a slower motor delivers more torque and is built in a larger frame.

Step 3: Understand the Load Type

  • Constant torque: Conveyors, hoists, positive-displacement pumps and compressors need full torque across the speed range, including at start.
  • Variable torque: Centrifugal pumps and fans need little torque at low speed. Their power rises with the cube of speed.
  • High inertia: Crushers, large fans and centrifuges take a long time to accelerate. Starting time and starting heat, not running load, often decide the motor size.

Step 4: Match the Duty Cycle

Standard ratings assume S1 continuous duty. Applications that start and stop frequently, such as cranes, hoists and indexing conveyors, are intermittent duties (S3, S4) and must be specified with the number of starts per hour and the percentage of time the motor is energised. Frequent starts heat a motor far more than steady running.

Step 5: Check Site Conditions

Catalogue ratings apply up to a 40 °C ambient temperature and 1000 m altitude. Hotter sites or higher altitudes reduce cooling and require derating or a larger frame. Dust, moisture and washdown conditions decide the enclosure protection, covered in our IP rating and insulation class guide.

Step 6: Check Current and Starting Method

Full-load current for a three-phase motor is:

Current (A) = Power (kW) × 1000 ÷ (1.732 × Voltage × Efficiency × Power factor)

A 7.5 kW motor on 415 V at 89% efficiency and 0.84 power factor draws about 14 A. On direct-on-line starting, a cage induction motor typically draws six to seven times that current for a few seconds. Star-delta starting reduces both starting current and starting torque to roughly one third, so it suits loads that start light, such as centrifugal pumps and fans, but not loaded conveyors.

Avoid Oversizing

Induction motors are generally most efficient between 75% and 100% of rated load. A motor that spends its life at 40% load runs at a low power factor and gives up the efficiency you paid for. Size to the calculated load plus a modest margin, then select the next standard rating.